Honeywell C6097 Pressure
Switch |
|
SKU:HWC6097
|
Description and Specs |
The Honewell C6097 Series Replaces many of the now Discontinued C437
series pressure switches.
Key Specifications
- Diaphragm-actuated safety limit switches
- Available ranges: 0.4—5" WC, 3—21" WC, 12—60" WC or 1.5—7
PSI
- IP54 enclosure with removable transparent cover protects
scale plate and adjusting knob, 1/4" NPT mount
- Switch ratings: 3.0 AFL, 18.0 ALR, 5.0 Amps resistive;
Switch can be wired to turn on alarms
- UL listed, CSA listed, FM approved, IRI acceptable
- Operating temperature range: -40° to 140°F
Break Action |
Operating Range |
Pressure Differential at Min. Setpoint |
Pressure Differential at Max. Setpoint |
Switch Operation |
Pressure Connection |
Mounting |
Full Part Number |
On Pressure Fall |
0.4" to 5" WC |
0.6" WC | 0.25" WC |
Manual Reset |
1/8" NPT |
1/4" NPT |
HWC6097A1095 |
0.4" to 5" WC |
— | — |
Auto Recycle |
1/8" NPT |
1/4" NPT |
HWC6097A1004 |
3" to 21" WC |
— |
— |
Auto Recycle |
1/8" NPT |
1/4" NPT |
HWC6097A1053 |
12" to 60" WC |
— | — |
Auto Recycle |
1/8" NPT |
1/4" NPT |
HWC6097A1079 |
On Pressure Rise |
3" to 21" WC |
2.4" WC | 4.2" WC |
Manual Reset |
1/8" NPT |
1/4" NPT |
HWC6097B1028 |
12" to 60" WC |
10" WC | 12" WC |
Manual Reset |
1/8" NPT |
1/4" NPT |
HWC6097B1002 |
1.5 to 7 PSI |
1.1" WC | 1.4" WC |
Manual Reset |
1/8" NPT |
1/4" NPT |
HWC6097B1051 |
1.5 to 7 PSI |
— | — |
Auto Recycle |
1/8" NPT |
1/4" NPT |
HWC6097B1101 |
|
|
|
©
2003-2009 Industrial Process and Sensor. All rights reserved.