About    Home Page    Order Info    Thermocouples    Legal/Privacy    Contact  

The products listed represent only a small selection of the available IPS product line.
To discuss your specific application with an experienced technician.

Please Call 618-465-7623

<< Product 4 of 12 >>
Flowline DataLoop II Intrinsically Safe Meter

Flowline DataLoop II Intrinsically Safe Meter



Please Call 1-618-465-7623 for a Quote on this product!

Description
Offered in intrinsically safe and general purpose configurations, the loop powered panel meter displays engineering units connected in series with one 4-20 mA transmitter. Select the LI25-2001 meter for hazardous applications with an intrinsically safe level transmitter. Select the LI25-1001 meter for general purpose applications. For field mount installations, order the single or two meter NEMA box.

Specifications
Display type:
LCD, 5-digit
Display units:
Engineering
Decimal point:
Floating
Display output:
-99999 to 999999
Display height:
0.6" (15 mm)
Backlight:
LED, bright orange
User interface:
Four push button
Sensor input:
(1) 4-20 mA transmitter
Loop power:
12-30 VDC
Memory:
Non-volatile
Voltage drop:
2.0 VDC w/o backlight
5.7 VDC w/backlight
Ambient temp.:
-40° to 149°
C: -40° to 65°
Enclosure type:
1/8 DIN, panel mount
Enclosure rating:
NEMA 4X (IP65) faceplate
Enclosure mat'l:
Polycarbonate
Classification:
LI25-2001: Intrinsically safe
LI25-1001: General purpose
Approvals (LI25):
FM, CSA: Class I, Div I,
Groups A, B, C, D; Class II,
Div I, Groups E, F, G; Class III,
Div I; Class I, Zone 0, Group IIC;
T-code = T4